Shijiazhuang Hanqian Technology Co., Ltd. is one of the leading manufacturers and suppliers of disc‑type flanged steam trap in China. With abundant experience, we are committed to providing high quality customized valves with competitive price. If you're going to wholesale durable disc‑type flanged steam trap made in China, welcome to get quotation from our factory.
Disc type flange steam trap is a thermodynamic steam trap with flange connection. Driven by flow velocity and pressure difference between steam and condensate, the disc plate opens and closes to automatically drain condensate from steam pipelines and prevent steam leakage. Compact and simple structure with high pressure resistance and fast response. It is suitable for intermittent drainage, widely used in main steam lines, tracing pipelines and small heat exchange equipment.
Main Features
- Thermodynamic principle: Driven by pressure difference generated by medium flow, the disc plate traps steam and drains condensate automatically with sensitive action.
- Flange connection: Flange joint for firm installation, easy disassembly and maintenance, stable pressure bearing.
- Compact structure: Fewer parts and small size, high pressure resistance, strong back pressure resistance, wide applicable differential pressure range.
- High temperature resistance: Stable performance under high-temperature steam, low risk of jamming and little maintenance.
- Debris-proof design: Some models are equipped with built-in strainer to block welding slag and protect disc plate.
Specification
| Body Material | WCB Cast Steel / 304 Stainless Steel optional |
| Internal Parts | Stainless Steel |
| Connection Type | Flange |
| Nominal Diameter | DN15~DN100 |
| Nominal Pressure | PN16, PN25, PN40, Class150~Class600 |
| Applicable Medium | Steam, condensate |
| Working Temperature | -29℃ ~ 425℃ |
| Standards | GB/T, API, ASME B16.5, ASME B16.34 |
Applications
Steam tracing pipelines, main steam transmission lines, small heaters, drying equipment, petrochemical industry and heating networks.
Notes
1. Can be installed horizontally or vertically. Medium flow must follow the marking on valve body.
2. A strainer is recommended on upstream to avoid scratches on disc plate and internal leakage.
3. Not suitable for large continuous condensate drainage. Preferred for pipelines with intermittent condensate generation.
4. Pay attention to backpressure limit. Excessive backpressure will affect normal operation.
5. Do not operate beyond rated temperature and pressure. Periodically check for internal steam leakage.
Hot Tags: disc‑type flanged steam trap, China disc‑type flanged steam trap manufacturers, suppliers, factory